67 - Fire Inspector II Exam 온라인 연습
최종 업데이트 시간: 2026년04월21일
당신은 온라인 연습 문제를 통해 International Code Council Fire Inspector II 시험지식에 대해 자신이 어떻게 알고 있는지 파악한 후 시험 참가 신청 여부를 결정할 수 있다.
시험을 100% 합격하고 시험 준비 시간을 35% 절약하기를 바라며 Fire Inspector II 덤프 (최신 실제 시험 문제)를 사용 선택하여 현재 최신 87개의 시험 문제와 답을 포함하십시오.
정답:
Explanation:
Exit Announcements in Motion Picture Theaters
According to the International Fire Code (IFC) 2021, Section 403.9.1.2, motion picture theaters must provide an audible announcement informing occupants of exit locations no more than 5 minutes prior to the start of each program.
This requirement ensures that audience members are aware of exit locations in case of an emergency, enhancing fire safety in crowded venues.
정답:
Explanation:
The maximum travel distance allowed in a one-story Group F-2 (Factory Industrial - Low Hazard) occupancy with automatic sprinklers and automatic smoke and heat vents is regulated by 2021 International Fire Code (IFC) Table 1017.2 C Exit Access Travel Distance.
IFC Table 1017.2 C Maximum Travel Distance:
For a Group F-2 occupancy equipped with an automatic sprinkler system, the maximum allowable exit access travel distance is 400 feet.
However, when automatic smoke and heat vents are installed, the travel distance is limited to 350 feet.
This is because while the sprinklers control fire spread, smoke and heat vents help with smoke control, allowing for extended egress distances but not as much as without them.
Why Other Options Are Incorrect?
A. 250 ft. C Too restrictive; the IFC allows a longer travel distance in this scenario.
B. 300 ft. C Less than the allowed 350 ft.
D. 400 ft. C Only applicable without smoke and heat vents.
정답:
Explanation:
Reference to Liquid-Level Limit Control Requirements for Atmospheric Tanks:
According to The International Fire Code (IFC 2021), Section 5704.2.7.5, atmospheric tanks containing hazardous materials must be equipped with a liquid-level limit control if their capacity exceeds 500 gallons.
This requirement ensures that overfilling is prevented, reducing the risk of hazardous spills, leaks, and fire hazards.
Purpose of Liquid-Level Limit Controls:
These controls automatically shut off or alert operators when the liquid level reaches a predetermined limit.
They prevent tank overfill and reduce the risk of hazardous material release, which can cause fires, explosions, or environmental contamination.
Clarification of Incorrect Answer Choices:
A. 55 gallons # Incorrect
55-gallon drums are not subject to the same overfill protection requirements as large atmospheric tanks.
B. 100 gallons # Incorrect
Too low based on IFC 5704.2.7.5, which sets the requirement at 500 gallons.
C. 250 gallons # Incorrect
Some local regulations may require monitoring for tanks of this size, but IFC specifies 500 gallons as the mandatory threshold.
Conclusion:
The correct and verified answer is D (500 gallons) based on IFC 5704.2.7.5, ensuring proper overfill protection for atmospheric tanks containing hazardous materials.
정답:
Explanation:
LP-Gas Storage Limits for Dealers in Non-Public Buildings
According to the International Fire Code (IFC) 2021, Section 6109.9, the maximum allowable quantity of LP-gas in containers stored by a dealer awaiting resale in a building that is not open to the public is 2,000 pounds of water capacity.
This limit is intended to reduce fire and explosion hazards in enclosed spaces while allowing reasonable storage for commercial purposes.
정답:
Explanation:
Retention of Fire Inspection Records
The International Fire Code (IFC) and NFPA 1 specify that records related to fire inspections, violations, and compliance must be maintained for the lifetime of the building.
This ensures a continuous history of inspections, violations, and fire prevention measures, which is critical for enforcement, legal action, and future compliance reviews.
정답:
Explanation:
IFC Section 105.6 lists activities requiring operational permits. For A, lumber storage exceeding 100,000 board feet (bd. ft.) indoors or outdoors requires a permit (Section 105.6.28, Lumber Yards), but local thresholds may be lower―85,000 bd. ft. is close to this limit and likely exceeds typical exempt amounts, triggering a permit in many jurisdictions. For B, IFC Table 3206.2 allows small quantities of combustible commodities like baled cotton (100 cu. ft. is minimal) without a permit unless part of a larger high-piled storage operation. For C, fruit ripening with CO2 (Section 105.6.13) requires a permit only for specific flammable gases, not CO2 alone, which is nonflammable.
For D, organic coating production (Section 105.6.33) requires a permit only above 1 gallon per day, but 2 gallons is still small-scale and context-dependent―lumber storage is the clearer permit trigger here. Thus, A is the best answer.
정답:
Explanation:
Reference to Flammable Liquids Storage Cabinet Requirements:
According to The International Fire Code (IFC 2021), Section 5704.3.2 and NFPA 30 (Flammable and Combustible Liquids Code), Section 9.5.3, the maximum amount of Class II and Class III liquids that can be stored in a flammable liquids storage cabinet is 120 gallons.
This limit ensures safe containment, fire protection, and reduced risk of liquid ignition or spillage.
Understanding Class II and III Liquids:
Class II liquids: Flash point between 100°F and 140°F (e.g., diesel fuel, kerosene).
Class III liquids: Flash point above 140°F (e.g., motor oil, cooking oils).
While these liquids are less volatile than Class I liquids, they still pose a fire risk, requiring proper storage in approved cabinets.
Clarification of Incorrect Answer Choices:
A. 10 gallons # Incorrect
Too low; IFC and NFPA allow up to 120 gallons in storage cabinets.
B. 60 gallons # Incorrect
This is the maximum for Class I liquids, but Class II and III liquids are allowed up to 120 gallons.
D. 240 gallons # Incorrect
Exceeds the allowable limit per IFC 5704.3.2 and NFPA 30, which set the maximum at 120 gallons per cabinet.
Conclusion:
The correct and verified answer is C (120 gallons) as per IFC 5704.3.2 and NFPA 30, ensuring compliance with flammable liquids storage safety standards.
정답:
Explanation:
A fire code official has authority to enter buildings for fire safety inspections, but they must comply with legal entry requirements. The Fourth Amendment of the U.S. Constitution and fire codes restrict entry without permission, an administrative warrant, or legal authority.
Fire code officials do NOT have the right to enter vacant buildings at any time without proper authorization.
Reference to Fire Inspector Documentation:
정답:
Explanation:
Storage of fine magnesium scrap is regulated under 2021 IFC Chapter 59 C Magnesium and specifically IFC Section 5904.3.2.5 C Separation Distances for Magnesium Scrap Storage.
IFC 5904.3.2.5 C Minimum Separation Distances:
Fine magnesium scrap in quantities greater than 1,000 cubic feet must be separated from all buildings (except those used for magnesium scrap recovery) by at least 250 feet.
Why Other Options Are Incorrect?
A. 30 feet C Too close; insufficient for high-risk metal fires.
B. 50 feet C Does not meet the minimum required separation for magnesium scrap.
C. 100 feet C While larger, it still does not meet the 250-ft. requirement
정답:
Explanation:
The requirement for panic hardware on exit doors is specified in 2021 IFC Section 1010.2.9 C Panic and Fire Exit Hardware.
IFC Section 1010.2.9.1 C Where Panic Hardware is Required:
Panic hardware is required for Group A (Assembly) occupancies when the occupant load is 50 or more.
It is also required in certain Group E (Educational) and Group R-1 (Hotels and Dormitories) occupancies under specific conditions.
Why Other Options Are Incorrect?
A. 10; A C The threshold for panic hardware in Group A occupancies is 50, not 10.
C. 50; M C Group M (Mercantile) does not require panic hardware unless specifically required by another section of the code.
D. 100; F C Panic hardware is not required in Group F (Factory) occupancies at 100 occupants; the threshold applies primarily to Group A.
정답:
Explanation:
In automobile refinishing spray booths where drying by heat occurs inside the same spray booth, fire codes require interlocks to prevent ignition hazards.
Before activating the drying apparatus, the ventilation system must purge the booth of spray vapors for at least 5 minutes to remove flammable concentrations.
Reference to Fire Inspector Documentation:
정답:
Explanation:
Aisle Width Requirements for Baled Fiber Storage
According to the International Fire Code (IFC) 2021, Section 3206.9, blocks or piles of baled fiber must be separated by aisles at least 5 feet wide to allow for proper fire department access and fire prevention measures.
This regulation applies to combustible fibers such as cotton, jute, and hemp, which are highly flammable and can quickly contribute to fire spread.
정답:
Explanation:
Reference to Fire-Flow Requirements for Type IIB Buildings:
The International Fire Code (IFC 2021), Appendix B, Table B105.1(2) establishes the minimum fire-flow requirements for buildings based on construction type, size, and the presence of sprinkler systems.
For a 75,000 sq. ft. Type IIB (non-combustible, unprotected) building without sprinklers, the required fire-flow is 5,500 gpm for 4 hours.
Why Fire-Flow Matters:
Fire-flow ensures that sufficient water is available to control and extinguish fires in large buildings.
Type IIB buildings lack built-in fire resistance enhancements, making adequate fire-flow crucial.
Clarification of Incorrect Answer Choices:
A. 3,000 gpm for 3 hours # Incorrect
Too low for a building of this size and construction type.
B. 4,000 gpm for 4 hours # Incorrect
Below the required 5,500 gpm per IFC Appendix B.
D. 5,750 gpm for 4 hours # Incorrect
Slightly above the requirement but not the exact minimum mandated by IFC Table B105.1(2).
Conclusion:
The correct and verified answer is C (5,500 gpm for 4 hours) as per IFC Appendix B, Table B105.1(2), ensuring compliance with fire-flow standards for Type IIB buildings without sprinklers.
정답:
Explanation:
The fire-resistance rating requirements for different building elements in Type IV (Heavy Timber) construction are specified in the 2021 International Building Code (IBC), Table 601 C Fire-Resistance Rating Requirements for Building Elements (Hours).
IBC Table 601 C Fire Resistance for Type IV Construction:
Interior nonbearing walls and partitions in Type IV construction require 0 hours of fire resistance.
This is because Type IV construction primarily relies on large, heavy timber elements that provide inherent fire resistance.
Why Other Options Are Incorrect?
B. 1 hour C Incorrect, as nonbearing interior walls in Type IV construction are not required to have a fire-resistance rating.
C. 1-1/2 hours C Not required by code.
D. 2 hours C Only structural elements like exterior walls in some cases may require fire resistance, but nonbearing interior partitions do not.
# Correct Answer
A. 0 hours
정답:
Explanation:
Flammable Liquid Storage Limits in Control Areas
According to the International Fire Code (IFC) 2021, Section 5003.1.1 and Table 5003.1.1(1), the allowable quantity of flammable liquids stored in a control area can be doubled if the building is equipped with an automatic sprinkler system that complies with NFPA 13.